Fire alarm systems - Esser

Control panel IQ8Control M

Esser 808004

The modular IQ8Control M fire alarm computer uses proven technology and fulfils the highest security requirements for the comprehensive protection of premises. Thus, it is just as suitable for use in medium sized premises with complex security requirements as it is for premises, which are spread over a wide area and are networked.
The IQ8Control M is ideally suited to medium-sized premises with complex
security requirements and for premises that cover a wide area and/or are networked. The IQ8Control M is completely compatible with the fire alarm system 8000 control panels. The modular design allows flexible and user-friendly integration of several individual modules, which together form one unit.

  • Max. five micromodules, with peripheral module Part No. 772477, up to five esserbus analog loop modules (system supports up to 635 digital loop addresses in total)
  • Max. seven micromodules, with extension module Part No. 772476, up to seven esserbus analog loop modules (system supports up to 889 digital loop addresses in total)
  • Short circuit and open circuit tolerant loop operation
  • Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
  • Up to 127 esserbus devices (fire detectors and/ or manual call points)/detector zones per loop
  • Up to 32 esserbus transponders per loop/operation of wireless components (see chapter 10)
  • Operation types TM and PM as per DIN VDE 0833 – 2 to avoid unwanted alarms being triggered
  • Fire brigade operating panel and transmission interface on the peripheral module
  • Three common relays, freely programmable, monitored, floating for up to 30 V DC/1A (on the peripheral module)
  • TTY or RS 485 or RS 232 interface
  • Integration in the short circuit and open circuit resistant essernet network with up to 31 fire detection panels depends on transmission rate
  • Connection to graphical supervisor WINMAG via serial essernet interface (SEI)
  • Operating panel with alphanumerical display
  • Large LCD display with 8 rows x 40 characters
  • Event memory for up to 10,000 events
  • All Systems 8000 micromodules are compatible
  • Printer interface for internal printer
  • Two batteries with monitoring circuit
  • Monitored input for external power supply unit


Additional features for powered loop:

  • Max. 6 analog powered loops and expandable up to 127 loop devices (per loop) in mixed mode/ loop powered and non-loop powered (system supports up to 762 digital loop addresses in total)
  • esserbus PLus (Powered Loop) supplied, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54 – 3 with alarm tone as per DIN 33404
  • Up to 48 powered loop base sounders (series 9200) per loop
  • Up to 32 powered loop IQ8Alarm per loop
  • Up to 48 IQ8Quad with alarm device per loop

The IQ8Control M as an efficient fire alarm control panel (FACP) for the property supervision of mid-sized to large objects, facilitates simultaneous detection, control and alarm signaling both on the analog ring as well as on the spur.
The loop operation type of the panel (powered-loop or non-powered-loop) can be selected via a jumper located on the power supply card. Depending on which loop operation type has been selected, the corresponding analog module/modules should be used.

Details - Control panel IQ8Control M

Distribution Esser

Talk to a technical sales consultant.