Blueprint
Compact EVAC audio system certified EN54-16 and EN54-4. 2x250W power with backup for 2 zones 100V with dual A/B routing.
Front has 4.3’ touch screen display, PTT handheld microphone, status indication LED, two USB sockets for mp3 file playback, and built-in loudspeaker for local verification of audio played in the various zones. Input has 8 monitored contacts, AUX1 and AUX2 RCA type, 1 balanced analogue audio with priority contact for PABX or pre-amplified microphone bases.
At the output it has 3 configurable relay outputs, 1 0 dB audio signal for connection to a high fidelity system. It allows signal equalisation for each audio source and independent volume control for each zone. Up to 9 microphone stations can be connected to the system and up to 6 EVALL series systems can be connected via RS485 BUS.
Prepared for wall mounting and, with optional accessories, also for rack mounting. Dimensions (W x H x D) in mm 430 x 710 x 280, weight 21.9 kg (without batteries).
MAIN FEATURES:
- Model EV500
- Number of audio zones (No.) 2
- Number of amplifiers (No.) 2
- Backup amplifier (reserve) YES ‘Preserve Amp.
- Option for automatic backup amplifier intervention YES
- Speaker line for each zone A and B (line redundancy) YES
- RJ45 socket for LINK connection between control units YES
- Maximum number of control panels in the link 6
- Emergency front microphone input YES
- No. BUS lines for connecting microphone stations 3 (BUS EMG, BUS SRV, BUSP)
- Emergency stations connection with RJ45 connection YES
- No. of stations that can be connected to the EMG BUS (Emergency) 2
- Connection of service stations with RJ45 connection YES
- No. of stations connectable to the SRV BUS (Service) 7
- No. of stations connectable to the BUSP (Service for BMS21 with 1 RJ25 connector) 8
- No. AUX analogue inputs (RCA) for connecting external audio sources 2
- No. USB ports for music playback (MP3 files) 2
- Balanced analogue input (PABX) with priority contact on music YES
- Audio signal output “o dB” 1
- 1 W front speaker YES
- Signal equalisation for each audio source YES
- Continuous microphone capsule monitoring YES
- No. of Log events 4096 per Log (Fault and System)
- Multi-language display menu YES
- Standards EN54-4, EN54-16
Details - EVAC AUDIO SYSTEM EV500
- ★★★★★
- Category Evacuation systems
- Brand Blueprint