Evacuation systems - Blueprint

EVAC AUDIO SYSTEM EV500

Blueprint

Compact EVAC audio system certified EN54-16 and EN54-4. 2x250W power with backup for 2 zones 100V with dual A/B routing.

Front has 4.3’ touch screen display, PTT handheld microphone, status indication LED, two USB sockets for mp3 file playback, and built-in loudspeaker for local verification of audio played in the various zones. Input has 8 monitored contacts, AUX1 and AUX2 RCA type, 1 balanced analogue audio with priority contact for PABX or pre-amplified microphone bases.

At the output it has 3 configurable relay outputs, 1 0 dB audio signal for connection to a high fidelity system. It allows signal equalisation for each audio source and independent volume control for each zone. Up to 9 microphone stations can be connected to the system and up to 6 EVALL series systems can be connected via RS485 BUS.

Prepared for wall mounting and, with optional accessories, also for rack mounting. Dimensions (W x H x D) in mm 430 x 710 x 280, weight 21.9 kg (without batteries).

MAIN FEATURES:

  • Model EV500
  • Number of audio zones (No.) 2
  • Number of amplifiers (No.) 2
  • Backup amplifier (reserve) YES ‘Preserve Amp.
  • Option for automatic backup amplifier intervention YES
  • Speaker line for each zone A and B (line redundancy) YES
  • RJ45 socket for LINK connection between control units YES
  • Maximum number of control panels in the link 6
  • Emergency front microphone input YES
  • No. BUS lines for connecting microphone stations 3 (BUS EMG, BUS SRV, BUSP)
  • Emergency stations connection with RJ45 connection YES
  • No. of stations that can be connected to the EMG BUS (Emergency) 2
  • Connection of service stations with RJ45 connection YES
  • No. of stations connectable to the SRV BUS (Service) 7
  • No. of stations connectable to the BUSP (Service for BMS21 with 1 RJ25 connector) 8
  • No. AUX analogue inputs (RCA) for connecting external audio sources 2
  • No. USB ports for music playback (MP3 files) 2
  • Balanced analogue input (PABX) with priority contact on music YES
  • Audio signal output “o dB” 1
  • 1 W front speaker YES
  • Signal equalisation for each audio source YES
  • Continuous microphone capsule monitoring YES
  • No. of Log events 4096 per Log (Fault and System)
  • Multi-language display menu YES
  • Standards EN54-4, EN54-16

Details - EVAC AUDIO SYSTEM EV500

Distribution Blueprint

Talk to a technical sales consultant.