Fire alarm systems - Esser

OT multisensor fire detector

O²T Serie IQ8Quad

Esser 802373

Multisensor fire detector with integrated optical sensor and heat sensor which give both a combined signal as well as a separate heat signal for improved false alarm management, with time-controlled signal analysis and weighted data combination of both detector functions for detecting smoldering fires and fires with extreme heat generation. Intelligent detector with decentralized intelligence, self-function test, CPU redundancy mode, automatic adaptation to the environments, alarm and operating data storage, alarm indication and soft addressing. The loop isolator is integrated in the detector. A parallel detector indicator is additionally attachable.

Dual technology optical/thermal detector, IQ8Quad series.
Can be connected directly to the esserbus® loop.

  • Thermal component alarm threshold: 54°C.
  • Continuous monitoring of optical chamber and sensor electronics status, including continuous monitoring of CPU functionality.
  • Automatic drift compensation in case of variations due to critical environmental conditions (e.g. dust and/or humidity).
  • Presence of experimental false alarm algorithms which, when properly compared with the environmental information collected, allow the false alarms to be eliminated and not evaluated as fire alarms.
  • By means of further specific algorithms, the detector is able to identify any electromagnetic disturbances generated by equipment such as inverters, conveyor belts, radio/wireless equipment and audio speakers.
  • Integrated short-circuit isolator.
  • Two-colour LED for evaluation of operating and alarm status.
  • Thermal sensor operating class: A2.
  • Degree of protection: IP40 extendable to IP 43.
  • Ring identification colour: White.

Details - OT multisensor fire detector

Distribution Esser

Talk to a technical sales consultant.